Model |
Air-cooled Refrigeration |
Water-cooled Refrigeration |
HRRF012-A-20 |
HRRF018-A-20 |
HRRF012-A-20 |
HRRF018-A-20 |
Cooling method |
Air-cooled refrigeration |
Water-cooled refrigeration |
Refrigerant |
R454C (HFO/HFC, GWP: 146) |
Refrigerant charge [kg] |
0.30 |
0.22 |
Weight [kg] |
45 |
Control method |
PID control |
Ambient temperature/Humidity/Altitude |
Temperature: 5 to 40°C, Humidity: 30 to 70%, Altitude: less than 3000 m |
Circulating fluid system |
Circulating fluid |
Tap water, 15% ethylene glycol aqueous solution |
Set temperature range [°C] |
5 to 35 |
Cooling capacity (50/60 Hz) [W] |
1000/1200 |
1600/1800 |
1000/1200 |
1600/1800 |
Heating capacity (50/60 Hz) [W] |
450/500 |
Temperature stability [°C] |
±0.1 |
Pump capacity (50/60 Hz) [MPa] |
0.13 (at 7 L/min)/0.18 (at 7 L/min) For Option T: 0.42 (at 10 L/min)/0.4 (at 14 L/min) For Option MT: 0.32 (at 10 L/min)/0.32 (at 14 L/min) For Option T1: 0.28 (at 10 L/min)/0.28 (at 10 L/min) |
Rated flow (50/60 Hz) [L/min] |
7/7 For Options T, MT: 10/14, For Option T1: 10/10 |
Flow display range [L/min] |
2 to 16 |
Electric conductivity display range [μS/cm] |
0.1 to 48 (Only for Option DM) |
Electric conductivity setting range [μS/cm] |
0.5 to 45 (Only for Option DM) |
Particle filter nominal filtration rating [μm] |
5 |
Bypass valve |
Installed |
Tank capacity [L] |
Approx. 4 |
Outlet, Return port size |
Rc1/2 |
Drain port size |
Rc1/4, With cap |
Leakage protection |
Drain pan (With water leakage sensor) |
Fluid contact material |
Stainless steel, Copper (Heat exchanger brazing), Brass∗16, SiC, Alumina ceramic, Carbon, PP, PE, POM, PA, FKM, EPDM, PVC, PPS, AS, Fluoropolymer, Ion exchange resin |
Facility water system |
Temperature range [°C] |
- |
5 to 40 |
Pressure range [MPa] |
0.3 to 0.5 |
Required flow rate (50/60 Hz) [L/min] |
8 |
12 |
Inlet-outlet pressure differential of facility water [MPa] |
0.3 or more |
Port size |
Rc3/8 |
Fluid contact material |
Stainless steel, Copper (Heat exchanger brazing), Bronze, Brass, NBR, EPDM |
Electrical system |
Power supply |
Single-phase 200 to 230 VAC, 50/60 Hz, Allowable voltage range ±10% |
Circuit protector [A] |
10 For Options T, MT, T1: 15 |
Applicable earth leakage breaker capacity |
Rated current: 10 A For Options T, MT, T1: 15 A Sensitivity current: 30 mA |
Cable quantity x Size (Including grounding cable) |
3 cores x 14 AWG (3 cores x 2.0 mm2) |